[3]SCU调试问题记录

开关采集APP

  1. 物模型: 光禄坊试点物模型RCD_KF, 其它地方 RCD_FZ

  2. 测点未上报IOT原因: 模型文件isReport需要默认1,该模型文件在容器目录,未开放到/data/app/breaker目录

  3. 台账配置: 开关台账需要配置/data/app/db/104param.json文件,设备列表,例如:

         {
             "devNo":    "10",
             "port":    "PLC",
             "addr":    "100000000001",
             "model":    "RCD_KF",
             "desc":    "",
             "protocol":    "rcd_KF",
             "manuID":    "daqo",
             "isreport":    "1"
         },
    
  4. IOT配置: 光禄坊#1台区IOT配置文件:

     [OBJECTINFO]
     OBJECT = HUAWEI_SHANDONG
     GATEWAYID = 1311021380010101
     GETURL = http://192.168.1.130:8080/iot/devices/auth/gateway
    
     [BROKERINFO]
     HOST = 172.17.0.1
     PORT = 30011
     CLINETID = D11597116uwGBF 
     USERNAME = 9C37452231F84144ABEBA14695E0981A 
     PASSWORD = E9OZ9r0O8CR8CP(ic]wq{n3a 
    
     [TIMEOUT]
     QUERY_REG       = 600 
     AUTO_REPORT     = 600 
     AUTO_REPORT_YC  = 6000 
     TOTAL_REPORT    = 90000 
     UPDATE_ONLINE   = 0 
    
     [CONFIG]
     ADD_DEV_FAIL_COUNT = 10
     LOST_CONNECTION_RESTART = 0
     KEEPALIVEINTERVAL = 180
     ENABLE_4G_INFO_SEND = 0
    
     [DEBUG]
     DEBUG_LEVEL = 1
    
  5. HPLC福建模式问题
    目前智芯还未完全适配福建版HPLC,需要强制切换成国网模式才能正常运行,目前可使用的切换程序进行操作,使用方法:
    切换说明 需要注意,关闭c_cco容器

下载文件:rs485_test_scu

超时参数:
超时参数 需要注意,调试时如果开关较多,需要确定HPLC超时时间设置是否合理,建议设置24S,也就是24000。

  1. 凯帆框架开关

现场环境: 2个开关,地址分别为1,2;
通讯参数: 9600,8,N,1
通讯协议: KFW3-智能控制器通信协议Modbus.pdf

碧海银滩调试

1.终端重启原因,/etc/SysAppList.json关闭logserver服务和blecli蓝牙服务; 2.breaker app IOT无法上报,容器里RCD_FZ.json中isreport置1; 3.